Carrier TV-ISO-E2 TruVu Isolated Network Router User Guide
TruVu Isolated Network Router
Part Number: TV-ISO-E2
Specifications
BACnet Conformance
Conforms to the BACnet Router (B-RTR) Standard Device and BACnet Broadcast Management Device
(B-BMD). Tested to and listed to Protocol Revision 19 (135-2016).
i-Vu Version
Compatible with i-Vu Version 9.0 or later
Power Requirements
24 Vac 10%, 50–60 Hz, 50 VA
24 Vdc 10%, 18 W
Communication Ports
Primary Port: 10/100 BaseT, full duplex, Ethernet ports for BACnet/IP, BACnet/IPv6, BACnet/Ethernet,
BACnet/SC communication.
Isolated Port: 10/100 Mbps BaseT, full duplex, Ethernet port for BACnet/IP
Port S1: High-speed EIA-485 port for communication with BACnet MS/TP network at 9,600 to 115,200 bps
Port S2: High-speed EIA-485 port for communication with a BACnet MS/TP network at 9,600 to 115,200 bps.
End of Net termination can be set to Yes to terminate the network segment.
Service port: USB 2.0 port for setting up the router and troubleshooting through a local connection to a
computer, connecting to the Equipment Touch, or a wireless service adapter.
Environmental
-40 to 158°F (-40 to 70°C), 10–95% relative humidity, non-condensing. The TV-ISO-E2 can be installed both
inside and outside the building envelope. It should be placed in a UL listed enclosure. If installed outside, the
enclosure must be suitable for the environmental conditions.
Operating Range
LED Status Indicators
Tricolor NET LED to show network status / Tricolor SYS LED to show system status/POWER LED/S1 EON
LED/S2 EON LED/A TX (Transmit) and RX (Receive) LED for: Port S1 and Port S2
Router Addressing
Memory
Webserver interface
8 GBs eMMC Flash memory (120 MB available for use) and 512 MB DDR3 RAM. User data is archived to
non-volatile Flash memory when parameters are changed, every 90 seconds, and when the firmware is
deliberately restarted.
Real Time Clock
Compliance
Real-time clock keeps track of time in the event of a power failure for up to 3 days.
United States: FCC compliant to Title CFR47, Part 15, Subpart B, Class A. UL Listed, File E143900; CCN
PAZX, UL916, Energy Management Equipment; UL Listed to UL864: Smoke Control System. AS/NZS: RCM
Mark 61000-6-3; Canada: UL Listed File E143900, CCN PAZX7, CAN/CSA C22.2 No. 205 Signal Equip.,
Industry Canada Compliant, ICES-003, Class A; UL Listed to ULC-S527: Smoke Control System. Europe/
UKCA: CEN50491-5-2:2009; Part 5-2: Compliant with Electromagnetic Compatibility Regulations - Gov. UK
and RoHS for Electrical and Electronic Equipment 2012 RoHS Compliant: 2015/863/EU REACH Compliant
Protection
Device is protected by a replaceable, fast acting, 250 Vac, 3A, 5mm x 20mm glass fuse.
The power and network ports comply with the EMC requirements EN50491-5-2
Enclosure
Mounting
Fire-retardant ABS, UL94-5VA
35mm DIN rail mounting or screw mounting
Dimensions
Overall
A: 5.51 in. (14 cm)
D: 5.88 (14.93 cm)
E: 4.41 (11.20 cm)
Depth: 2.01 in. (5.11 cm)
Weight: .75 lbs. (.3402 kg)
Screw Mounting
B: 3.00 in. (7.62 cm)
C: 5.29 in. (13.44 cm)
For more information, contact
your local Carrier Controls Expert.
Controls Expert Locator:
© Carrier 2025. All Rights Reserved. Cat. No. 11-808-1165-01 06/25
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs, without notice and
without incurring obligations. Trademarks are properties of their respective companies and are hereby acknowledged.
| General | Details |
|---|---|
| Name | Carrier TV-ISO-E2 TruVu Isolated Network Router User Guide |
| Make | Carrier |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.1 MB |
If you have any questions regarding Carrier TV-ISO-E2 TruVu Isolated Network Router User Guide, please ask here and describe the problem in detail.