LEDs
LED
Color
Activity
Function
Continuously ON
Continuously OFF At least one internal power supply out
Device ready.
RUN
Green
HMI/Tool
RUN
FLT
of range.
Start-up of device.
Flashing
FLT
Red
--
Continuously OFF OK
Continuously ON
HW fault or program fault.
Flashing
--
Incorrect or corrupt FW.
(Not used)
INF
COM1
Yellow Flashing
Sends MS/TP packages.
Sends LONWORKS packages
(PXG3.L only).
COM2
SVC
Flashing
Yellow
Red
Continuously OFF Configured.
Continuously ON
Flashing
Defective Hardware.
Unconfigured.
Flashing per wink
command *)
Physical identification of the router.
Ethernet Green Continuously ON
1 / 2
Link active
Continuously OFF Link inactive
Flashing
Network activity
Yellow Continuously ON
Link 100 Mbps
8 7 6 5 4 3 2 1
Continuously OFF Link 10 Mbps
9222z02
21s
*) Wink command
pattern:
5 Hz
1s
5 Hz
1s
2s
2s
Service button
Button Press
Description
Physical identification on the network (Ethernet).
Short
1
Proceed as follows to reset the device to a factory state:
1. Power off device.
2. Power on device.
3. Wait for all LEDs to light up and turn off again,
then push the SVC button.
1
4. Keep SVC button pressed until all LEDs light up, then release.
Up to Desigo V6_SP (FW V01.15.15.144): Keep SVC button
pressed until the green RUN LED flashes, then release.
5. Wait for device to fully start up unconfigured
(RUN LED on, SVC LED flashes).
Any device passwords and other settings are lost.
4 / 10
PXG3... BACnet router for Ethernet - LONWORKS - MS/TP
CM1N9270en_12
| General | Details |
|---|---|
| Name | SIEMENS PXG3.L BACnet Router Instruction Manual |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.26 MB |
If you have any questions regarding SIEMENS PXG3.L BACnet Router Instruction Manual, please ask here and describe the problem in detail.