Home > Enertex > Enertex KNX IP Secure Router User Manual

Enertex KNX IP Secure Router User Manual

1164-EnertexKNXIPSecureRouter_US-6.odt, 2023-02-22  
Seite 16 von 19  
Read or configure the maximum length of the KNX TP telegrams. This may be necessary if  
there is an incorrect implementation of a TP stack. In that case the ETS may try to use  
telegrams with 248 bytes payload, but the TP device can not process (e.g. Zennio Z35i).  
Default is 248 and should only be changed if necessary.  
apdu [55..248]  
# apdu  
maximal len of a KNX telegram 248.  
Usage: apdu [55 .. 248]  
Read or configure maximum telegram rate (IP => TP); 50 T / s corresponds to 100% bus load.  
tpratemax [5..50]  
# tpratemax  
no limit, sending with maximum performance to TP.  
Usage: tpratemax [5 .. 50]  
Shows various statistics on device and bus status  
stats  
uptime: 114 days, 2:19  
KNX communication statistics:  
TX to IP (all)..: 333729 (ca. 233 t/m)  
TX to KNX.......: 23244 (ca. 16 t/m)  
RX from KNX.....: 94559 (ca. 66 t/m)  
Overflow to IP..: 0  
Overflow to KNX.: 0  
TX tunnel re-req: 260  
TP bus voltage..: 28.95 V  
TX TP rate......: 50 T/s (= 100 %)  
Uptime: Runtime of the interface since last restart  
TX to IP (all): Number of all telegrams sent on IP  
TX to KNX: Number of all telegrams sent on KNX  
RX from KNX: number of telegrams received from the KNX bus  
Overflow to IP: Number of telegrams that could not be sent to IP  
Overflow to KNX: Number of telegrams that could not be sent to the KNX bus  
TX tunnel re-req: Number of telegrams that had to be repeated in the tunnel connections  
TP bus voltage: Current bus voltage (at the time of calling stats)  
TX TP rate: maximum telegram rate (TP)  
Shows the bus load as follows:  
busload  
-------------------------------------------------  
Measure  | 1 min. |  5 min | 15 min | since start  
-------------------------------------------------  
RX Bit/s | 0035   | 0091   | 0080   | 0079    
TX Bit/s | 0007   | 0006   | 0002   | 0004    
RT Bit/s | 0042   | 0098   | 0083   | 0083    
-------------------------------------------------  
RX T/s   | 00.26  | 00.94  | 00.70  | 00.69    
TX T/s   | 00.12  | 00.08  | 00.03  | 00.05    
RT T/s   | 00.38  | 01.02  | 00.73  | 00.75    
-------------------------------------------------  
RX %     | 00.52  | 01.88  | 01.40  | 01.39    
TX %     | 00.24  | 00.16  | 00.07  | 00.11    
RT %     | 00.76  | 02.04  | 01.47  | 01.51    
-------------------------------------------------  
MaxR T/s | 08     | 08     | 24     | 29       
MaxT T/s | 03     | 03     | 03     | 08       
MxRT T/s | 08     | 08     | 24     | 29       
-------------------------------------------------  
Maximum load at 16:50:08 06.10.2020 (UTC)  
Where RX is receive, TX is transmit, RT is the sum of receive and transmit according to this  
table every minute, 5 minutes, 15 minutes, and since the device was started.  
Bit/s shows the actual baud rate on the TP bus. It is the total of bytes of the application data  
and offset of the KNX protocol layers.  
The % load is related to 50 telegrams per second.  
The maxima are recalculated in the given interval.  
Enertex® Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - Germany - mail@enertex.de  
GeneralDetails
NameEnertex KNX IP Secure Router User Manual
MakeEnertex
LanguageEnglish
FiletypePDF (Download)
File size0.44 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding Enertex KNX IP Secure Router User Manual, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

eleven − eight =

Enertex KNX IP Secure Router User Manual