Home > VIMAR > VIMAR 01507 By me KNX Router Instruction Manual

VIMAR 01507 By me KNX Router Instruction Manual

BUILDING AUTOMATION  
System Requirements - Product description  
1. System Requirements  
To create the network system, make sure all the devices (switch, router, firewall, etc.) are configured in such a way as to allow the passage of multicast messages the device  
sends on IP. We recommend you involve an IT manager to make sure the KNX/By-me system can operate in the IP solution of the connections.  
2. Product description  
The By-me/KNX router enables communication between parts of a system comprising By-me devices, grouped together within an “island”, with a system comprising KNX  
devices. The messages are transmitted in both directions according to criteria which define the correspondence of the communication objects belonging to the specific  
domains. The router allows up to 500 routing rules. Each rule is specified by the By-me group address, by the KNX address, by the direction of communication (from KNX  
to By-me; from By-me to KNX; both) and by the type of information exchanged (1 bit, 2 bit, …).  
The device is equipped with a TP terminal for connection to the By-me BUS, an Ethernet connector and a front push button for configuration via ETS. The power supply is  
provided by the By-me BUS.  
Router 01507 conforms to the KNX Secure requirements on the datapoints defined in the routing table. A datapoint on the KNX side can be defined for the heartbeat signal.  
2.1 Front view of the device  
A: Ethernet KNX over IP line connector  
A
B: Ethernet KNX over IP line status LED  
C: By-me BUS line status LED  
D: Traffic on Ethernet KNX over IP line LED  
01507  
E: Traffic on By-me BUS line LED  
ROUTER IP KNX  
F: GA LED  
B
State  
C
G: PA LED  
IP  
TP  
H: Reset push button  
I: Configuration LED  
D
F
Traffic  
GA  
E
PA  
L: Configuration push button  
M: By-ME BUS line  
G
S
TP  
IP  
X
H
Program  
BUS  
I
L
M
2.2  
LED indications  
Green  
ON: Correct operation  
Red  
ON: Device factory reset  
Ethernet KNX over IP line status LED (B)  
By-me BUS line status LED (C)  
Ethernet KNX over IP line traffic LED (D)  
Traffic on By-me BUS line LED (E)  
GA LED (F)  
ON: Data traffic presence  
-
-
-
ON: Device not configured  
PA LED (G)  
Configuration LED (I)  
ON: Device in the configuration phase  
4
GeneralDetails
NameVIMAR 01507 By me KNX Router Instruction Manual
MakeVIMAR
LanguageEnglish
FiletypePDF (Download)
File size0.63 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding VIMAR 01507 By me KNX Router Instruction Manual, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

three × one =

VIMAR 01416 Automation IP Video Entry System Router User Manual
VIMAR 01416 Automation IP Video Entry System Router User Manual

VIMAR 01507 By me KNX Router Instruction Manual