Enabling Learning Mode to Auto Start  
If Learn Ready reports NOT READY because of currently unfavorable  
temperatures, you may enable the AFMS to automatically start Learning Mode  
when it detects favorable temperatures later (overnight is likely).  
1. Leave Min Delta Temp set to the default or adjust it if needed.  
NOTE: If the ΔT becomes less than Min Delta Temp, the AFMS controller will  
abort Learning Mode. This is to ensure that the controller does not  
receive unusable learning samples. Setting Min Delta Temp at a 15°F or  
larger difference is recommended.  
2. Leave Auto Start Delta Temp set to the default, or adjust it if needed.  
NOTE: When the ΔT reaches the Auto Start Delta Temp, Learning Mode will  
start. Learning Mode will complete if the ΔT remains greater than the  
Min Delta Temp for the entire duration. An Auto Start Delta Temp that is  
at least 20°F more than Min Delta Temp is recommended.  
3. Leave Time Between Samples (Seconds) set to the default or adjust it if  
needed.  
NOTE: Most often, Time Between Samples (Seconds) can be left on the default  
(60 seconds). You might increase the value if the damper Stroke Time  
is longer than that of a typical unit, or if the damper actuator requires  
extra time to respond.  
4. For Auto Learn Enable, select ON.  
5. Click Save.  
6. Wait for Learning Mode to complete during favorable temperatures  
(overnight is likely).  
Skip to Verify Learning Mode Completed and Record Date on page 10.  
Verify that AFMS Status is in Learning Mode  
On the Monitor page, in the Operation group, verify whether AFMS Status reports  
LEARN MODE.  
Verify Learning Mode Completed and Record Date  
After the AFMS completes Learning Mode (approximately 2 hours), on the Learn  
page:  
1. Locate the Date of Last Learn (YYMMDD).  
2. Enter the date into the Note Sheets for AFMS Checkout and Commissioning.  
Skip to Access the AFMS Table and Record Data on page 11.  
10  
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C  
GeneralDetails
NameKMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide
MakeKMC CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.27 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

14 + 18 =

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide