POINT-TO-POINT CHECKOUT TASKS
The steps for each point-to-point checkout task are presented in subsections
below. Complete each task/subsection in the order presented.
Set Control Mode to Damper Position Control
On the Configure page, in the System Setup group:
1. For Control Mode, select DMPR POSITION CTRL from the drop-down menu.
2. Click Save.
Verify Pressure Transducer Settings
Do the following for all pressure transducers (supply and pressure assist) that
were installed, following their manufacturer’s installation instructions:
1. Verify that the signal output type is set to volts.
2. Verify that the transducer is set to unipolar mode.
3. If the transducer has several pressure range options, verify that the correct
range is set (according to the pressure range of the unit).
Make Pressure Transducer Zero Adjustment
Zero out all pressure transducers (supply and pressure assist) that were
installed, following their manufacturer’s installation instructions.
You will need to expose the transducer high and low ports to ambient pressure
by temporarily removing the tubing from the ports. After zeroing the transducer,
reconnect each tube to the correct port.
Set the Supply Air Differential Pressure Range (5901-
AFMS only)
On the Configure page, in the General group:
1. For SA DP Range, enter the maximum inches of water column that the
supply air pressure transducer can measure.
NOTE: For example, a TPE-1475-21, can measure up to 2” wc, so enter 2. A
TPE-1475-22 can measure up to 10” wc, so enter 10. (A 9311-AFMS can
measure up to 2” wc.) Some AFMS installations may use other pressure
transducers.
2. Click Save.
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C
3
| General | Details |
|---|---|
| Name | KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide |
| Make | KMC CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.27 MB |
If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual

KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual