10. Once the actuator stops moving, visibly verify that the damper is fully open.  
If the actuator is moving the damper in reverse (i.e. 10 volts = closed), see the  
next section, “Set Damper Reverse Action”.  
Set Damper Reverse Action (if needed)  
If visual inspection (see the previous section) revealed that the damper actuator  
moves in reverse action (i.e. 10 volts = closed), on the Configure page, in the  
Damper group:  
1. For Damper Reverse Action, select REVERSE from the drop-down menu.  
2. Click Save.  
(if needed)  
Stroke Damper and Verify that Reported Damper Position  
Follows  
1. Go to Configure > the System Setup group:  
2. Ensure that DMPR POSITION is set for Control Mode.  
3. For Damper Setpoint, enter 0.  
4. Click Save.  
5. Once the actuator stops moving, visibly verify that the damper is fully  
closed.  
6. Go to the Monitor tab.  
7. Verify that Damper Position (in the Operation group) reports a value within  
±1% of 0.  
NOTE: The inclinometer can detect very small movements of the damper  
assembly.  
8. Go to the Configure tab again.  
9. For Damper Setpoint, enter 50.  
10. Click Save.  
11. Once the actuator stops moving, visibly verify that the damper is 50% open/  
closed.  
12. Go to the Monitor tab again.\  
13. Verify that Damper Position reports a value within ±1% of 50.  
14. Go to the Configure tab again.  
15. For Damper Setpoint, enter 100.  
16. Click Save.  
17. Once the actuator stops moving, visibly verify that the damper is now fully  
open.  
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C  
7
GeneralDetails
NameKMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide
MakeKMC CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.27 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

11 + 15 =

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide