Home > KMC CONTROLS > KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide

Set the Supply Air Area  
On the Configure page, in the General group:  
1. For Supply Air Area:  
• If the supply air pickup tubes were installed on the supply air fan bell,  
enter the square foot measurement of the fan inlet.  
• If the supply air pickup tubes were installed in the supply air duct, enter  
the square foot measurement of the duct cross-section where the tubes  
are located.  
NOTE: For assistance calculating the area, use the Free Area Calculator in the  
Note Sheets for AFMS Checkout and Commissioning.  
2. Click Save.  
Inspect Pressure Assist Pickup Tubes (PA only)  
For pressure assist applications, ensure that the pickup tubes were installed in  
the correct location per the AFMS installation guide.  
Calibrate the Supply Air Flow  
On the Tune page, in the Calibration group:  
1. Do any of the following:  
• In the Offset column for Supply Air Flow, enter the CFM offset (determined  
by a TAB technician) for the supply air pressure transducer.  
• In the Multiplier column for Supply Air Flow, enter the multiplier (deter-  
mined by a TAB technician) for the supply air pressure transducer.  
2. Click Save.  
Calibrate OAD/RAD Diff. Pressure (pressure assist only)  
For pressure assist applications, on the Tune page, in the Calibration group:  
1. In the Offset column for OAD Diff. Pressure / RAD Diff. Pressure, enter  
the differential pressure offset (determined by a TAB technician) for the  
pressure assist pressure transducer.  
2. Click Save.  
or  
4
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C  
GeneralDetails
NameKMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide
MakeKMC CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.27 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

4 + 1 =

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide