18. Go to the Monitor tab again.
19. Verify that Damper Position reports a value within ±1% of 100.
If Damper Position reports values that are the opposite of the entered Damper
Setpoint, see the next section, “Set Inclinometer Action to Reverse”.
Set Inclinometer Action to Reverse (if needed)
For the standard (AMSO) application or OAD Pressure Assist (AMSOP)
application, if the inclinometer was mounted on a horizontal return air damper
blade because the outside air damper blades are vertical, then you need to set
Inclinometer Action to REVERSE.
If testing revealed that Damper Position reports values that are the opposite of
the Damper Setpoint (see the previous section), on the Configure page, in the
Damper group:
1. For Inclinometer Action, select REVERSE from the drop-down menu.
2. Click Save.
(if needed)
Damper span calibration is completed. Continue to the Learning Mode Tasks on
page 9.
8
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C