18. Go to the Monitor tab again.  
19. Verify that Damper Position reports a value within ±1% of 100.  
If Damper Position reports values that are the opposite of the entered Damper  
Setpoint, see the next section, “Set Inclinometer Action to Reverse”.  
Set Inclinometer Action to Reverse (if needed)  
For the standard (AMSO) application or OAD Pressure Assist (AMSOP)  
application, if the inclinometer was mounted on a horizontal return air damper  
blade because the outside air damper blades are vertical, then you need to set  
Inclinometer Action to REVERSE.  
If testing revealed that Damper Position reports values that are the opposite of  
the Damper Setpoint (see the previous section), on the Configure page, in the  
Damper group:  
1. For Inclinometer Action, select REVERSE from the drop-down menu.  
2. Click Save.  
(if needed)  
Damper span calibration is completed. Continue to the Learning Mode Tasks on  
page 9.  
8
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C  
GeneralDetails
NameKMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide
MakeKMC CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.27 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

five − 3 =

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide