Verify and Calibrate Outside Air Temperature
On the Tune page, in the Calibration group:
1. Locate the OAT sensor’s reading, next to Outside Air Temp.
2. Using a NIST-traceable instrument, measure the temperature near the OAT
sensor.
3. Compare the two values.
4. Enter the Offset for Outside Air Temp.
5. Click Save.
Verify and Calibrate Return Air Temperature
On the Tune page, in the Calibration group:
1. Locate the RAT sensor’s reading, next to Return Air Temp.
2. Using a NIST-traceable instrument, measure the temperature near the RAT
sensor.
3. Compare the two values.
4. Enter the Offset for Return Air Temp.
5. Click Save.
Verify and Calibrate Mixed Air Temperature
On the Tune page, in the Calibration group:
1. Locate the MAT sensor’s reading, next to Mixed Air Temp.
2. Using a NIST-traceable instrument, measure the temperature near the MAT
sensor.
3. Compare the two values.
4. Enter the Offset for Mixed Air Temp.
5. Click Save.
Point-point-checkout is completed. Continue to the Damper Span Calibration
Tasks on page 6.
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C
5
| General | Details |
|---|---|
| Name | KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide |
| Make | KMC CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.27 MB |
If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual

KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual