DAMPER SPAN CALIBRATION TASKS
After completing the Point-to-Point Checkout Tasks on page 3, calibrate the
damper span. The steps for each damper span calibration task are presented in
subsections below. Complete each task/subsection in the order presented.
Set the Damper Stroke Time
On the Configure page, in the Damper group:
1. For Stroke Time, enter the time (in seconds) that it takes for the actuator to
move the damper from fully closed to fully open.
2. Click Save.
Set the Actuator Voltage Range
On the Configure page, in the Damper group:
1. For Actuator Voltage, select the voltage range of the damper actuator from
the drop-down menu (2 to 10 volts or 0 to 10 volts).
2. Click Save.
Turn On Learn Damper Span, then Verify
Before the AFMS can run Learn Mode, it must learn the minimum and maximum
incline of the damper using the inclinometer. The Learn Damper Span sequence
will take 3 to 5 minutes to complete.
On the Configure page, in the Damper group:
1. For Learn Damper Span, select ON from the drop-down menu.
2. Click Save.
3. After 3 to 5 minutes, verify that Damper Span Learned reports LEARNED.
Stroke Damper and Visibly Verify Positions
On the Configure page, in the System Setup group:
1. Ensure that DMPR POSITION is set for Control Mode.
2. For Damper Setpoint, enter 0.
3. Click Save.
4. Once the actuator stops moving, visibly verify that the damper is fully
closed.
5. For Damper Setpoint, enter 50.
6. Click Save.
7. Once the actuator stops moving, visibly verify that the damper is 50% open/
closed.
8. For Damper Setpoint, enter 100.
9. Click Save.
6
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C
| General | Details |
|---|---|
| Name | KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide |
| Make | KMC CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.27 MB |
If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual

KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual