INTRODUCTION  
This document guides users through checkout and commissioning of an Airflow  
Measurement System (AFMS). It is designed to aid in completing the tasks on  
the Note Sheets for AFMS Checkout and Commissioning.  
The BAC-5051(A)E router can be used to configure, control, tune, and monitor  
the operation of an AFMS. AFMS features are accessible through the Balancing  
/ AFMS / ZEC web page and are active once a valid AFMS controller has been  
discovered.  
NOTE: The default IP address of the BAC-5051(A)E router is 192.168.1.252.  
PREREQUISITES  
1. Install the AFMS (the controller and all system components).  
NOTE: See the AFMS installation guide found on any AFMS controller’s product  
page.  
2. Select the application (on the AFMS controller) needed for the equipment.  
NOTE: See the AFMS selection guide for a table listing the configuration tools  
that can be used to select the application. Select the application before  
configuring other settings. Changing applications after configuration  
will restore most parameters to their defaults.  
3. Set the AFMS controller’s communication parameters.  
NOTE: See the AFMS selection guide for a table listing the configuration tools  
that can be used to set the communication parameters.  
4. Configure the router and set up routing to the AFMS controller.  
NOTE: See the Application and Installation Guide for the BAC-5051AE Router  
for details.  
ACCESSING THE AFMS PAGES  
1. Log in to the router using a web browser.  
NOTE: See the Application and Installation Guide for the BAC-5051AE Router  
for details.  
2. Go to Advanced > Balancing / AFMS / ZEC.  
3. For Instance Range, in Start, enter the device instance that was set for the  
AFMS controller.  
NOTE: End automatically fills with a value, making a range of 50 device  
instances.  
4. Click Discover.  
5. Click the circle next to the AFMS controller’s Instance.  
NOTE: The selected AFMS controller highlights and the AFMS configuration  
page tabs appear below.  
2
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C  
GeneralDetails
NameKMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide
MakeKMC CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.27 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

fifteen + fourteen =

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide