Set Control Mode  
On the Configure page, in the System Setup group:  
1. For Control Mode, select from the drop-down menu the option that will be  
the AFMS’s normal mode for this installation:  
OA FLOW CTRL: The AFMS modulates the damper actuator to maintain  
the Outside Air Flow Setpoint (CFM).  
PASS THROUGH: The AFMS passes control of the damper actuator to  
another controller. (The AFMS measures and monitors only.)  
MAT CTRL: The AFMS modulates the damper actuator to maintain the  
Mixed Air Temp Setpoint (°F/°C).  
2. Click Save.  
ABOUT TESTING AND BALANCING AFMS  
If everything was installed and configured correctly prior to running Learning  
Mode, the AFMS Table data is very reliable. The AFMS uses the same method  
from ASHRAE Standard 111 (Section 7.6.3.3, “Flow Rate Approximation by  
Temperature Ratio”) that a good tester and balancer should use. Furthermore, as  
the AFMS performs the method, it takes the OAT, RAT, and MAT measurements  
simultaneously and several times for reliable averages, increasing the reliability  
of the data.  
However, should verification be required, the following guidelines should be  
observed:  
• Make measurements using NIST-traceable instruments.  
• Use the method from ASHRAE Standard 111, Section 7.6.3.3, “Flow Rate  
Approximation by Temperature Ratio” to calculate the table data.  
• Should an adjustment be needed, adjust single data items from the AFMS  
Table rather than making a linear adjustment.  
NOTE: TAB OA Factor (found in the Calibration group under Tune) should be at 1  
and not adjusted.  
If large adjustments need to be made to the AFMS Table data, one or more of the  
sensors may have been installed incorrectly and/or a setting was misconfigured  
prior to running Learning Mode. The problem should be corrected by fixing the  
installation and/or configuration, then running Learning Mode again.  
12  
BAC-5051(A)E Pages for Configuring an AFMS, AG230819C  
GeneralDetails
NameKMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide
MakeKMC CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.27 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

2 × two =

KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS Conquest BAC-5051AE BACnet Router Instruction Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual
KMC CONTROLS BAC-5051AE BACnet Router Owner’s Manual

KMC Controls BAC-5051 TRUEFIT Measurement System Router User Guide