TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide

Setting AFMS Parameters  
Before Beginning  
Before setting an AFMS's parameters in AFMS, ensure that the Prerequisites on page 3 have been met.  
Setting the Parameters  
Select the Configure tab.  
1.  
For Supply Area, enter the measurement (in square feet) of the cross section where the supply airflow pickup  
2.  
tubes were installed.  
Choose to either leave Enable Low Limit set to ON (the default), or to turn it OFF.  
3.  
4.  
Either leave Low Temp Limit set to the default (37°F), or adjust the value.  
For Stroke Time (Seconds), enter the time (in seconds) that it takes for the damper to go from 100% open to  
100% closed.  
5.  
6.  
For Damper Reverse Action:  
o
Select NORMAL if the greater the output signal to the damper actuator is, the more the damper opens (if  
10 volts = 100% open).  
o
Select REVERSE if the greater the output signal to the damper actuator is, the more the damper closes (if  
10 volts = 100% closed).  
For Actuator Voltage, select the voltage range of the damper actuator (2 to 10 volts or 0 to 10 volts).  
7.  
8.  
Select ON for Learn Damper Span.  
AFMS BAC-5051(A)E Router AG  
5
AG230818A  
GeneralDetails
NameTRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
MakeTRUEFIT
LanguageEnglish
FiletypePDF (Download)
File size0.2 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

fifteen − four =

TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide