Setting AFMS Parameters
Before Beginning
Before setting an AFMS's parameters in AFMS, ensure that the Prerequisites on page 3 have been met.
Setting the Parameters
Select the Configure tab.
1.
For Supply Area, enter the measurement (in square feet) of the cross section where the supply airflow pickup
2.
tubes were installed.
Choose to either leave Enable Low Limit set to ON (the default), or to turn it OFF.
3.
4.
Either leave Low Temp Limit set to the default (37°F), or adjust the value.
For Stroke Time (Seconds), enter the time (in seconds) that it takes for the damper to go from 100% open to
100% closed.
5.
6.
For Damper Reverse Action:
o
Select NORMAL if the greater the output signal to the damper actuator is, the more the damper opens (if
10 volts = 100% open).
o
Select REVERSE if the greater the output signal to the damper actuator is, the more the damper closes (if
10 volts = 100% closed).
For Actuator Voltage, select the voltage range of the damper actuator (2 to 10 volts or 0 to 10 volts).
7.
8.
Select ON for Learn Damper Span.
AFMS BAC-5051(A)E Router AG
5
AG230818A