TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
Running AFMS Learning Mode
Before Starting Learning Mode
For valid results, first ensure that:
l
The parameters are set correctly. (See Setting AFMS Parameters on page 5.)
l
The sensors are calibrated. (See Calibrating the AFMS's Sensors on page 7.)
l
The supply air fan is running at a normal, steady rate (without hunting or sporadic spikes).
l
If the unit has a heat recovery wheel, it is turned off.
l
If any heating or cooling sources are located upstream of the MAT sensor, they are turned off.
l
If the unit has a bypass damper, it is set to 100% open.
Checking Learn Ready Status
Select the Learn tab.
1.
Take note whether Learn Ready reports READY or NOT READY.
2.
Interpreting Learn Ready Status
If READY is reported, you may manually start Learning Mode. (Continue to Manually Starting Learning Mode
on page 9.)
If NOT READY is reported:
l
Check Sensor Fault. If FAULT is reported, fix any faults found.
l
Ensure that Learn Damper Span has completed.
l
Mixed Air Temp Low Limit Control may be ACTIVE. If that is the case, continue to Enabling Learning
Mode to Auto Start on page 9.
AFMS BAC-5051(A)E Router AG
8
AG230818A