Running AFMS Learning Mode  
Before Starting Learning Mode  
For valid results, first ensure that:  
l
The parameters are set correctly. (See Setting AFMS Parameters on page 5.)  
l
The sensors are calibrated. (See Calibrating the AFMS's Sensors on page 7.)  
l
The supply air fan is running at a normal, steady rate (without hunting or sporadic spikes).  
l
If the unit has a heat recovery wheel, it is turned off.  
l
If any heating or cooling sources are located upstream of the MAT sensor, they are turned off.  
l
If the unit has a bypass damper, it is set to 100% open.  
Checking Learn Ready Status  
Select the Learn tab.  
1.  
Take note whether Learn Ready reports READY or NOT READY.  
2.  
Interpreting Learn Ready Status  
If READY is reported, you may manually start Learning Mode. (Continue to Manually Starting Learning Mode  
on page 9.)  
If NOT READY is reported:  
l
Check Sensor Fault. If FAULT is reported, fix any faults found.  
l
Ensure that Learn Damper Span has completed.  
l
Mixed Air Temp Low Limit Control may be ACTIVE. If that is the case, continue to Enabling Learning  
Mode to Auto Start on page 9.  
AFMS BAC-5051(A)E Router AG  
8
AG230818A  
GeneralDetails
NameTRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
MakeTRUEFIT
LanguageEnglish
FiletypePDF (Download)
File size0.2 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

five × 3 =

TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide