Controlling Airflow with an AFMS  
About  
After Setting Up an AFMS on page 4, you can control outside air flow, or control mixed air temperature. Also, for  
setup or maintenance purposes, you can command a damper position.  
Alternatively, you can pass through control of the damper actuator to an external controller, using the AFMS for  
measurement and monitoring only. (See Monitoring with an AFMS on page 13.)  
Controlling Outside Air Flow  
Select the Configure tab.  
1.  
2.  
3.  
4.  
From the Control Mode dropdown menu, select OA FLOW CTRL.  
Enter an Outside Air Flow Setpoint (as CFM).  
Select Save.  
Controlling Mixed Air Temperature  
From the tabs that appear, select Configure.  
From the Control Mode dropdown menu, select MAT CTRL.  
Enter a Mixed Air Temp Setpoint.  
1.  
2.  
3.  
4.  
Select Save.  
Commanding a Damper Position  
From the tabs that appear, select Configure.  
From the Control Mode drop-down menu, select DMPR POSITION CTRL.  
Enter an Outside Air Damper Setpoint (0–100% open).  
Select Save.  
1.  
2.  
3.  
4.  
AFMS BAC-5051(A)E Router AG  
11  
AG230818A  
GeneralDetails
NameTRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
MakeTRUEFIT
LanguageEnglish
FiletypePDF (Download)
File size0.2 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

1 × 4 =

TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide