Label  
Description  
If the saved Control Mode is MAT CTRL (see Controlling Mixed Air Temperature on  
page 11), FAULT will display if Mixed Air Temp is more than 15°F off from the Mixed  
Air Temp Setpoint for longer than the Stroke Time (Seconds) (found under Configure >  
Damper). This indicates that the damper is not moving properly.  
Mixed Air Flow Fault  
FAULT = The calculation of the airflow based on the damper characterization data (see  
Accessing the Damper Characterization Table on page 15) has differed from the  
calculation using the current temperatures by more than the tolerance (20% difference  
default) for longer than 10 minutes. Ensure that the equipment is in the same physical  
condition as it was when Learning Mode was run. Learning Mode may need to be run  
again and/or sensors re-calibrated.  
Outside Air Flow Fault  
ACTIVE = The damper is modulating toward closed to prevent freezing of the equipment  
because the Mixed Air Temp is lower than the Low Temp Limit (found under Configure  
> General).  
Mixed Air Temp Low Limit  
Control  
INACTIVE = Either the Mixed Air Temp is higher than the Low Temp Limit, or Enable  
Low Limit is set to OFF.  
See the related low limit information in Setting AFMS Parameters on page 5.  
AFMS BAC-5051(A)E Router AG  
14  
AG230818A  
GeneralDetails
NameTRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
MakeTRUEFIT
LanguageEnglish
FiletypePDF (Download)
File size0.2 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

ten − 1 =

TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide