TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
Accessing the Damper Characterization Table
Manually Entering Damper Characterization Data
While not ideal, the damper characterization data can be calculated and entered manually in the AFMS Table. This
should only be done if — in the allotted time for Setting Up an AFMS on page 4 — the ΔT is unlikely to be greater
than the Min Delta Temp for the duration of Learning Mode. In that case, for reliability, running Learning Mode at a
later available time is still recommended.
Accessing the AFMS Table
Select the Tune tab.
Interpreting the AFMS Table
Label
Description
Percentage (expressed as a decimal) of the supply airflow that is outside
airflow at the given outside air damper position
Flow
The pressure differential (in inches of water column) at the given outside air
damper position
Diff Pressure
(pressure assist application only)
See the AFMS documentation for pressure assist information.
Outside air damper at closed position
Outside air damper at 0–5% open
Outside Air Closed
Outside Air 5
Outside Air 10
Outside Air 15
Outside Air 20
Outside Air 30
Outside Air 40
Outside Air 50
Outside Air 60
Outside Air 70
Outside Air 80
Outside Air 90
Outside Air 100
Outside air damper at 5–10% open
Outside air damper at 10–15% open
Outside air damper at 10–20% open
Outside air damper at 20–30% open
Outside air damper at 30–40% open
Outside air damper at 40–50% open
Outside air damper at 50–60% open
Outside air damper at 60–70% open
Outside air damper at 70–80% open
Outside air damper at 80–90% open
Outside air damper at 90–100% open
Calculating the damper characterization data
Use the %OA equation found in ASHRAE Standard 111, section 7.6.3.3: "Flow Rate Approximation by Temperature
Ratio".
AFMS BAC-5051(A)E Router AG
15
AG230818A
| General | Details |
|---|---|
| Name | TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide |
| Make | TRUEFIT |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.2 MB |
If you have any questions regarding TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide, please ask here and describe the problem in detail.