TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
Monitoring with an AFMS
Accessing Monitoring
Select the Monitor tab.
Monitoring Operation
Label
Description
Outside Air Flow
The AFMS controller's current outside air CFM calculation displays here.
NORMAL = No faults are detected.
LEARN MODE = Learning Mode is ON. (See Running AFMS Learning Mode on page 8.)
SPAN MODE = Learn Damper Span is ON. (See Setting AFMS Parameters on page 5.)
SERVICE = One or more faults are detected. (See Monitoring Faults on page 13.)
AFMS Status
The saved Control Mode (OA FLOW CTRL, MAT CTRL, DMPR POSITION CTRL or
PASS THROUGH) displays here. (See Controlling Airflow with an AFMS on page 11.)
Control Mode
Damper Position
Occupancy
The damper's percentage open displays here.
The default is OCCUPIED. If an occupancy sensor is used and the served space is vacant,
UNOCCUPIED will display.
Outside Air Temp
Return Air Temp
Mixed Air Temp
The outside air temperature sensor's measurement displays here.
The return air temperature sensor's measurement displays here.
The mixed air temperature sensor's measurement displays here.
Monitoring Faults
Label
Description
Outside Air Sensor Fault
Return Air Sensor Fault
Mixed Air Sensor Fault
Sensor Fault
FAULT = The outside air temperature sensor is missing or shorted.
FAULT = The return air temperature sensor is missing or shorted.
FAULT = The mixed air temperature sensor is missing or shorted.
FAULT = One or more of the three temperature sensors is missing or shorted.
If the saved Control Mode is DMPR POSITION CTRL (see Commanding a Damper
Position on page 11), FAULT will display if the damper position is more than 15% off
from the Outside Air Damper Setpoint for longer than the Stroke Time (Seconds)
(found under Configure > Damper). This indicates that the damper is not moving
properly.
Damper Control Fault
If the saved Control Mode is OA FLOW CTRL (see Controlling Outside Air Flow on
page 11), FAULT will display if Outside Air Flow is more than 15% off from the Outside
Air Flow Setpoint for longer than the Stroke Time (Seconds) (found under Configure >
Damper). This indicates that the damper is not moving properly.
Outside Air Control Fault
AFMS BAC-5051(A)E Router AG
13
AG230818A