TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide

Monitoring with an AFMS  
Accessing Monitoring  
Select the Monitor tab.  
Monitoring Operation  
Label  
Description  
Outside Air Flow  
The AFMS controller's current outside air CFM calculation displays here.  
NORMAL = No faults are detected.  
LEARN MODE = Learning Mode is ON. (See Running AFMS Learning Mode on page 8.)  
SPAN MODE = Learn Damper Span is ON. (See Setting AFMS Parameters on page 5.)  
SERVICE = One or more faults are detected. (See Monitoring Faults on page 13.)  
AFMS Status  
The saved Control Mode (OA FLOW CTRL, MAT CTRL, DMPR POSITION CTRL or  
PASS THROUGH) displays here. (See Controlling Airflow with an AFMS on page 11.)  
Control Mode  
Damper Position  
Occupancy  
The damper's percentage open displays here.  
The default is OCCUPIED. If an occupancy sensor is used and the served space is vacant,  
UNOCCUPIED will display.  
Outside Air Temp  
Return Air Temp  
Mixed Air Temp  
The outside air temperature sensor's measurement displays here.  
The return air temperature sensor's measurement displays here.  
The mixed air temperature sensor's measurement displays here.  
Monitoring Faults  
Label  
Description  
Outside Air Sensor Fault  
Return Air Sensor Fault  
Mixed Air Sensor Fault  
Sensor Fault  
FAULT = The outside air temperature sensor is missing or shorted.  
FAULT = The return air temperature sensor is missing or shorted.  
FAULT = The mixed air temperature sensor is missing or shorted.  
FAULT = One or more of the three temperature sensors is missing or shorted.  
If the saved Control Mode is DMPR POSITION CTRL (see Commanding a Damper  
Position on page 11), FAULT will display if the damper position is more than 15% off  
from the Outside Air Damper Setpoint for longer than the Stroke Time (Seconds)  
(found under Configure > Damper). This indicates that the damper is not moving  
properly.  
Damper Control Fault  
If the saved Control Mode is OA FLOW CTRL (see Controlling Outside Air Flow on  
page 11), FAULT will display if Outside Air Flow is more than 15% off from the Outside  
Air Flow Setpoint for longer than the Stroke Time (Seconds) (found under Configure >  
Damper). This indicates that the damper is not moving properly.  
Outside Air Control Fault  
AFMS BAC-5051(A)E Router AG  
13  
AG230818A  
GeneralDetails
NameTRUEFIT BAC-5051A E Airflow Measurement System Router User Guide
MakeTRUEFIT
LanguageEnglish
FiletypePDF (Download)
File size0.2 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

10 − six =

TRUEFIT BAC-5051A E Airflow Measurement System Router User Guide