6 ETS database parameters  
The following parameters can be set in ETS.  
6.1  
“General” menu  
6.1.1 Activation/Deactivation of the programming mode with frontal pushbuttons  
Used to enable the activation/deactivation of the programming mode by simultaneously pressing the Pass  
GA and Pass PhA push-buttons. The programming push-button is always enabled, and is not affected by  
the configuration of the parameter in question.  
6.1.2 Forwarding telegrams manual function  
Used to enable and set the duration of the manual telegram forwarding function. When this function is  
enabled, press the Pass GA push-button to activate/deactivate the forwarding of telegrams with a group  
address, or press the Pass PhA push-button to activate/deactivate the forwarding of telegrams with a  
physical address. In both cases, the forwarding settings that have been configured (filter or block) are  
bypassed by manually activating the telegram forwarding operation.  
6.2  
“Routing (KNX -> IP)” menu  
This menu contains the parameters for configuring the behaviour of the device when the telegrams transit on  
the KNX BUS line, defining their blockage or forwarding towards the backbone.  
6.2.1 Group telegrams (main groups 0 to 13)  
Used to set the behaviour of the router during the transit of BUS telegrams sent to a main group address  
between 0 and 13. The values that can be set are:  
block  
If this value is set, all the telegrams that transit in the line/area handled by the router, and are being sent to a  
main group address between 0 and 13, are not forwarded to the backbone (IP).  
10  
           
GeneralDetails
NameGEWISS GW A9707 KNX/IP Router Installation Guide
MakeGEWiSS
LanguageEnglish
FiletypePDF (Download)
File size0.38 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

If you have any questions regarding GEWISS GW A9707 KNX/IP Router Installation Guide, please ask here and describe the problem in detail.

Leave a Reply

Your email address will not be published. Required fields are marked *

one × 1 =

GEWISS GW A9707 KNX/IP Router Installation Guide